Thermostat DR Behavior Model

Thermostat DR Behavior Model​

Module: insight (always on) | Role: Any member | Licence: Free+

Thermostat DR treats the building's thermal mass as a battery. The output is a delta profile (change vs normal HVAC operation), not an absolute load.

Source: EPRI demand response studies, ev.energy engineering calibration against utility DR event data, Nest/Google and Ecobee published thermostat DR performance data.

Three-Phase Model​

Each DR event runs three consecutive 1-hour phases (4 intervals each):

PhasePower Delta (default)Duration RangeTimingPurpose
Pre-charge+0.7 kW/home0.5-2 hoursBefore dr_startOver-condition building (pre-heat or pre-cool)
Reduction-1.0 kW/home1-4 hoursdr_start onwardsCurtail HVAC; thermal mass maintains comfort
Rebound+0.5 kW/home0.5-3 hoursAfter reductionHVAC restores setpoint (snapback)

Energy roughly balances: positive energy (pre-charge + rebound) ≈ 1.2x negative energy. ~80% thermal round-trip efficiency.

Pre-conditioning detail: Setpoint offset of -2°F / -1°C (range: 1-4°F), increasing load 20-40% above baseline depending on HVAC capacity.

Curtailment detail: Setpoint offset of +4°F / +2°C (range: 2-6°F), reducing load 50-80% below baseline (0.5-1.5 kW per household).

Recovery detail: Snapback ratio of 1.3x curtailed load (range: 1.1-1.5x), exponential decay returning to baseline over the recovery period.

HVAC Types​

TypeReduction per HomeBest SeasonRegion
heat_pump1.0 kWWinterUK (default)
ac0.9 kWSummerUS
resistance1.5 kWWinterUK

Seasonal HVAC Availability​

SeasonHeat PumpACResistance
Winter100%0%100%
Spring50%50%30%
Summer20%100%0%
Autumn70%30%60%

Effective homes = count x prob_compliance x seasonal_availability[hvac_type][season].

Default Parameters​

ParameterDefaultRangeNotes
reduction_kw_per_home1.0 kW0.5-1.5Based on Nest/Pecan Street data
precharge_factor0.70.3-1.0Pre-charge as fraction of reduction
rebound_factor0.50.3-0.8Rebound as fraction of reduction
prob_compliance0.30.0-1.00.3 for recurring, 0.7 for single event
hvac_typeheat_pumpheat_pump/ac/resistanceDetermines reduction kW and seasonal availability
seasonwinterwinter/spring/summer/autumnAffects HVAC availability
dr_start17:00HH:MMStart of reduction phase (unmanaged mode only)

Industry Compliance Benchmarks​

MetricBenchmarkSource
Event participation rate85-90%Enrolled customers who remain opted-in during event
Customer opt-out rate10-15% per eventCustomers who override setpoint during event
Average curtailment0.8-1.2 kW per homeAC cycling programs in cooling season
Snapback peak1.2-1.5x curtailed loadPost-event recovery demand
Event fatigue factor-2% per event per monthDeclining participation with frequent events

Source: Compiled from published utility DR program results, Ecobee/Nest/Honeywell published thermostat DR performance data, EPRI and LBNL demand response program evaluation reports.

Compliance Guidance (prob_compliance)​

The fraction of enrolled homes that actually deliver a load reduction. Captures: enrollment x occupancy x HVAC availability x override rate x technical success.

ScenarioRecommendedRationale
Default (recurring daily)0.3Conservative for sustained operation
Single well-designed event0.7Real-world best case (Nest/Ecobee data)
Occasional (10-15/season)0.5-0.6Standard utility program
Daily for 30+ days0.3-0.4Significant occupant fatigue
Contractual/commercial0.8-0.9Financial penalties for non-compliance

Key insight: 0.7 is a single-event best case. Real programs run ~12 events/season, not daily. The default 0.3 is honest about what repeating=True actually delivers.

Optimized Mode​

In optimized mode, each home's 3-hour unit profile is slid across all 96 daily positions. The algorithm picks the placement that minimizes variance of (target_load + unit). Large cohorts (>10,000 homes) batch to cap at 10,000 iterations. Homes naturally stagger to flatten peaks.

Limitations​

  • Building thermal mass varies enormously; single model cannot capture all building types
  • Customer behavior (opening windows, manual override) is not modeled
  • Multi-zone HVAC systems have more complex response patterns
  • Fixed phase durations (each phase is exactly 1 hour); real buildings have variable thermal time constants
  • Newer smart thermostat programs tend to outperform older direct load control
  • Climate and season heavily influence curtailment magnitude