Load Components (Always FIXED)​

Module: insight (always on) | Role: Any member | Licence: Free+

Load cohorts are always unmanaged — they represent "business as usual" consumption. All load profiles are deterministic (no randomness). EV charging is not included in load profiles; it is simulated separately as a flexible asset.


Residential — UK (Elexon NHH Settlement Profile Classes)​

ProfileTypeAnnual kWhDaily kWhPeak Time
PC1Domestic Unrestricted2,900~8Evening 18:00-20:00, morning 07:00-08:00
PC2Domestic Economy 74,200~11.5Overnight 00:00-07:00 (storage heating)

The default is PC1 (unrestricted domestic tariff).

Profile shape:

  • Morning peak: 07:00-09:00 (breakfast, getting ready)
  • Evening peak: 17:00-21:00 (cooking, entertainment, heating)
  • Overnight trough: 00:00-06:00
  • Seasonal variation: Winter consumption ~40-60% higher than summer

UK Seasonal Multipliers: Winter 1.35x, Spring 0.95x, Summer 0.70x, Autumn 1.00x.

Source: Elexon NHH Settlement Profile Classes (BSCP504), BEIS (now DESNZ) annual domestic consumption statistics. Half-hourly settlement data mapped to 15-minute simulation intervals.

Limitations: Profile classes are statistical averages; individual households vary significantly. Assumes gas heating (typical UK); all-electric homes would have higher/different profiles. Profile Class data is periodically updated by Elexon; values should be refreshed annually.


Residential — US (Climate-Based)​

ProfileRegionsAnnual kWhDaily kWhPeak Driver
us_mixedTX, NC, VA, IL11,000~30Afternoon AC + evening (DEFAULT)
us_hot_humidFL, LA, Gulf14,500~40AC dominant, 30% overnight AC
us_hot_dryAZ, NV12,500~34Extreme AC peak ~17:30, cool nights
us_coldNY, MA, MN9,000~25Morning heating, dual peaks
us_mildPacific NW, Coastal CA8,000~22Flattest profile, minimal AC

Profile shapes:

  • Summer-peaking regions: Afternoon AC load creates sharp 14:00-18:00 peak
  • Winter-peaking regions: Morning (07:00-09:00) and evening (17:00-20:00) heating peaks
  • Baseload: ~0.5-1.0 kW continuous (refrigeration, standby, etc.)

US Seasonal Multipliers (vary by climate):

ProfileWinterSpringSummerAutumn
us_hot_humid0.85x0.90x1.40x0.85x
us_hot_dry0.75x0.85x1.55x0.85x
us_mixed1.15x0.85x1.20x0.80x
us_cold1.35x0.90x0.95x0.80x
us_mild1.20x0.95x0.90x0.95x

Source: EIA Residential Energy Consumption Survey (RECS 2020), NREL End-Use Load Profiles project (hourly, all climate zones). Climate zone mapping follows IECC/ASHRAE conventions. Geo-detection feature maps user location to nearest climate zone for automatic defaults.

Limitations: Regional averages; individual homes vary widely by size, efficiency, occupancy. Electric heating assumptions affect winter profiles significantly.


Commercial — UK (Elexon PC3-PC8)​

PCTypeAnnual kWhPattern
PC3Small Commercial15,0009am-5pm plateau
PC4Commercial Economy 725,000Business hours + overnight heating
PC5Max Demand 0-20% LF8,000Very peaky, intermittent
PC6Max Demand 20-30% LF20,000Extended hours
PC7Max Demand 30-40% LF40,000Near-continuous operation
PC8Max Demand >40% LF80,00024/7 flat (supermarkets, industrial)

Building presets: small_office (PC3, 15k), retail_shop (PC3, 12k), medium_office (PC6, 80k), large_office (PC7, 250k), restaurant (PC6, 35k), warehouse (PC7, 30k), light_industrial (PC7, 100k), supermarket (PC8, 500k), hotel (PC8, 200k), school (PC5, 50k).

Source: UK commercial profiles from Elexon NHH settlement classes (PC3-PC8). Building type annual consumption from CIBSE benchmarks and BEIS non-domestic energy statistics.


Data Centres​

TypePUELoad FactorPattern
Hyperscale1.1585-95%Flat 24/7 (AI/cloud workloads)
Enterprise1.4060-90%+10% during business hours
Colocation1.3550-85%+15% during business hours

Cooling overhead = (PUE - 1.0) fraction, with seasonal variation: Winter 0.6x, Spring 0.85x, Summer 1.2x, Autumn 0.85x.

Source: PUE benchmarks from Uptime Institute Annual Survey and ASHRAE TC 9.9. Load factor ranges from IEA Data Centres and Data Transmission Networks report.


Block Loads​

Constant power for a defined window. Parameters: start_time (HH:MM), duration_hours (max 24), size_kw.

Use for modeling any fixed-schedule industrial or infrastructure load that doesn't fit the predefined categories.